| Swimming Pool / Spa Inspection Report Linn County Public Health 1020 - 6th Street SE Cedar Rapids, IA 52401 Phone: (319) 892-6000 Fax: (319) 892-6099 E-mail: health@linncountyiowa.gov |
Facility Name: Comfort Inn & Suites Airport
Title: FD Registration No: SP57-117-100 \ SP57-117-101 Type: Routine |
| Name: | Indoor Pool < 150 | Indoor Spa |
|---|---|---|
| Registration No: | SP57-117-100 | SP57-117-101 |
| Area (Sq. ft.): | N/A | N/A |
| Volume (Gallons): | N/A | N/A |
| Filter Type: | Sand | Sand |
| Filter Rate: | - | - |
| Turnover Rate: | - | - |
| Chlorine (Free): | 0.6 | 10.4 |
| ORP: | 7.5/727 | 7.4/713 |
| Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
||
| Chlorine (Total): | 0.8 | 11.6 |
| Chlorine (Combined): | 0.2 | 1.2 |
| Bromine: | - | - |
| Pool: 2-18ppm Spa: 4-18ppm | ||
| Cyanuric Acid: | NA | NA |
| Must be less than 80 ppm | ||
| pH: | <7.0 | >8.0 |
| Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
||
| Total Alkalinity: | unknown | 150 |
| Calcium Hardness: | >400 | >400 |
| Name: | Indoor Pool < 150 | Indoor Spa |
|---|---|---|
| Registration No: | SP57-117-100 | SP57-117-101 |
| Temperature (F): | 81 | 106 |
| Spa must not exceed 104° | ||
| Type of Disinfectant: | chlorine pucks | chlorine pucks |
| Disinfection make and model: | Pentair 300-29X | Pentair 300-29X |
| Drain Cover make and model: | Aquaguard 5000 12" square | Aquaguard 5000 12" square |
| Drain Cover exp. date: | July 2028? | July 2028? |
| CPO: | Jay Patel | Jay Patel |
| CPO exp. date: | 11-30-29 | 11-30-29 |
| 1. Facility in compliance with smoking ban? | |
| ( If no, complete complaint form ) | |
Notes: Routine pool inspection
-Pool and spa are closed due to free chlorine and pH being out of compliance, and high temp
-When chlorine and pH levels are back to normal, and spa temp is under 104, call me and I will come confirm the levels prior to re-opening
Please email a letter of correction stating how the violations listed below have been and/or will be corrected to James.Aamodt@linncountyiowa.gov within 30 days of this inspection.
| # | Section | Reference | Ref. Page | |
|---|---|---|---|---|
| 1) | Management/Personnel | Pool: | 15.4(6)f(4) | 24 |
| Spa: | 15.51(5)e(5) | 17 | ||
| Item: Dates and quantities of chemical additions must be included in Operational Records | ||||
| Comment: Please include chemical additions to pool log. | ||||
| 2) | Management/Personnel | Pool: | 15.4(6)f(5) | 24 |
| Spa: | 15.51(5)e(6) | 17 | ||
| Item: Dates when filters are backwashed, cleaned, or changed included in Operational Records | ||||
| Comment: Please include this in pool log. | ||||
| 3) | Management/Personnel | Pool: | 15.4(2)e | 8 |
| Spa: | 15.51(2)e | 11 and 12 | ||
| Item: The disinfectant and pH in the pool water shall be manually tested and documented each day within one-half hour of the pool opening and at least one other time throughout the day. Chlorine shall be between 1.0 & 8.0 and pH shall be between 7.0 & 7.8. If either of these levels are out of range, the pool shall be closed. | ||||
| Comment: Free chlorine and pH were below allowable level. Bring back to allowable levels and call me before opening pool. | ||||
| 4) | Management/Personnel | Pool: | 15.4(2)e | 8 |
| Spa: | 15.51(2)e | 11 and 12 | ||
| Item: The disinfectant and pH in the spa water shall be manually tested and documented each day within one-half hour of the spa opening and at least one other time throughout the day. Chlorine shall be between 2.0 & 8.0 and pH shall be between 7.0 & 7.8. If either of these levels are out of range, the spa shall be closed. | ||||
| Comment: Free chlorine and pH were above allowable levels. Bring back to allowable levels and call me before opening the spa. | ||||
| 5) | Management/Personnel | Pool: | 15.4(2)e | 8 |
| Item: The swimming pool and/or spa water shall be tested for total alkalinity at least once in each week that they are open for use. The swimming pool and/or spa shall be tested for calcium hardness, total chlorine and cyanuric acid (outdoor pools only) at least once in each month that they are open for use | ||||
| Comment: Please document these weekly/monthly tests in your pool log. | ||||
| 6) | Filtration/Recirculation | Pool: | 15.4(1)b(2) | 8 |
| Spa: | 15.51(1)a(4) | 8 | ||
| Item: Filters and pumps shall have operating pressure gauges | ||||
| Comment: Pool pump is missing pressure gauge. | ||||
| 7) | Filtration/Recirculation | Pool: | 15.4(1)b(4) | 8 |
| Spa: | 15.51(1)e | 9 | ||
| Item: Skimmer shall have an easily removable basket/screen upstream from any valve and have a Self-adjusting weir in place | ||||
| Comment: Please replace missing weir doors in pool and spa. | ||||
| 8) | Safety | Pool: | 15.4(4)f(4) | 17 |
| Item: A first-aid kit shall be equipped with: band-aids, sterile 4x4 bandage compress, self-adhering gauze bandage, disposable gloves, and a chemical cold press. | ||||
| Comment: Add band-aids, 4X4 gauze pads, and self adhering gauze (coban) to first aid kit. | ||||
| 9) | Safety | Spa: | 15.51(4)c(1) | 13 |
| Item: A thermometer shall be available to measure temperatures in the range of 80 degrees to 120 degrees. Spa shall be closed if the temperature is over 104 degrees F. | ||||
| Comment: Spa temperature was recorded at 106. Get manual thermometer to check temp. Spa must not exceed 104 in order to re-open. | ||||
| 10) | Safety | Pool: | 15.4(4)b(3) | 13 |
| Item: The lower end of each ladder rail shall be securely covered with a smooth nonmetallic cap. | ||||
| Comment: Ladder was missing one end cap. | ||||
| 11) | Safety | Pool: | 15.4(6)k | 25 |
| Spa: | 15.51(5)i | 18 | ||
| Item: Each member of staff shall sign off that they have reviewed SDS sheets along with the Emergency Action Plan annually. | ||||
| Comment: Please have staff review SDS sheets and EAP annually and sign off that they reviewed it. | ||||
| 12) | Safety | Pool: | 15.4(4)m(1) | 22 |
| Spa: | 15.51(4)j(1) | 15 | ||
| Item: Each electrical outlet in the deck, shower room, and pool water treatment equipment areas of a swimming pool or spa shall be equipped with a properly installed ground fault circuit interrupter (GFCI) at the outlet or at the breaker serving the outlet, and shall be tested at least once a month. Testing dates and results shall be recorded in the pool records. | ||||
| Comment: Ensure GFCI testing is done monthly and documented in pool log. | ||||
| Name | Date | ||
|---|---|---|---|
| Inspector: | Inspection: | ||
| Report Received By: | Received: | ||
| Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).