Swimming Pool / Spa
Inspection Report


Jones County Environmental Services
105 Broadway Place, Suite 11
Anamosa, IA 52205
Phone: (319) 462-4715 Fax: (319) 462-5302
E-mail: environmental@co.jones.ia.us
  Facility Name: Monticello Aquatic Center
Address: 811 S Cedar St.
Monticello, IA  52310
Person Contacted: Jacob Oswald
Title: CPO
Registration No: SP53-002-100 \ SP53-002-101 \ SP53-002-102
Type: Routine

Water Quality Information
Name: Out. Pool >= 1500 Out. Wad > 500 Out. Waterslide
Registration No: SP53-002-100 SP53-002-101 SP53-002-102
Area (Sq. ft.): 6000 900
Volume (Gallons): 40000
Filter Type: Sand Sand
Filter Rate: - -
Turnover Rate: - -
Chlorine (Free): 0.8 0.8
ORP: 769/7.4/79 703/74/78
Pool: 1-8ppm, ORP 700-880 mV
If less than 0.6ppm or greater than 8.0ppm = closure
Spa: 2-8 ppm ORP 700-880 mV
If less than 1.0ppm or greater than 8.0ppm = closure
Chlorine (Total): 0.8 0.8
Chlorine (Combined): 0 0
Bromine: - -
Pool: 2-18ppm Spa: 4-18ppm
Cyanuric Acid: <30 <30
Must be less than 80 ppm
pH: 7.4 7.4
Pool and Spa: 7.2ppm-7.8ppm
If less than 6.8 or greater than 8.2 = closure
Total Alkalinity: 60 50
Calcium Hardness: - -

 

Water Quality Information (continued)
Name: Out. Pool >= 1500 Out. Wad > 500 Out. Waterslide
Registration No: SP53-002-100 SP53-002-101 SP53-002-102
Temperature (F): 78 79
Spa must not exceed 104°
Type of Disinfectant: Caly hypo Cal Hypo
Disinfection make and model: becsys5 pulsar precision BECSYS 5 pulsar precision
Drain Cover make and model: Waterway Waterway
Drain Cover exp. date: 05/2033 05/2033
CPO: Jill Fylnn Jill Flynn
CPO exp. date: 01/31/2031 01/31/2031

Smoke Free Air Act
1. Facility in compliance with smoking ban?
( If no, complete complaint form )

Notes: Routine inspection.

Please install soap dispensers in locker room showers

Repair/replace broken pressure gauges for pumps in control room

Continue to minimize tripping hazards on the pool deck and monitor slip resistance on high dive steps.

# Section Reference Ref. Page
1) Filtration/Recirculation Pool: 15.4(1)b(2) 8
Spa: 15.51(1)a(4) 8
  Item: Filters and pumps shall have operating pressure gauges
  Comment: Main pump pressure gauges are broken
   
2) Showers/Toilets/Dressing Rooms Pool: 15.4(5)e 23
  Item: Soap shall be available at each lavatory and at each indoor shower fixture.
  Comment: Soap dispensers are missing in both locker room showers
   
  Name   Date
Inspector: Inspection:
     
Report Received By: Received:
Reviewed By: Reviewed:

These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).