| Swimming Pool / Spa Inspection Report Linn County Public Health 1020 - 6th Street SE Cedar Rapids, IA 52401 Phone: (319) 892-6000 Fax: (319) 892-6099 E-mail: health@linncountyiowa.gov |
Facility Name: Elmcrest Country Club
Title: CPO Registration No: SP57-015-100 \ SP57-015-101 Type: Routine |
| Name: | Outdoor Pool >= 1500 sq ft | Out. Wading Pool |
|---|---|---|
| Registration No: | SP57-015-100 | SP57-015-101 |
| Area (Sq. ft.): | 1500 | 1500 |
| Volume (Gallons): | 154000 | 2500 |
| Filter Type: | Sand | Sand |
| Filter Rate: | - | - |
| Turnover Rate: | - | - |
| Chlorine (Free): | 2.8 | 3.0 |
| ORP: | 735/7.6 | 711/7.7 |
| Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
||
| Chlorine (Total): | 3.0 | 3.2 |
| Chlorine (Combined): | 0.2 | 0.2 |
| Bromine: | - | - |
| Pool: 2-18ppm Spa: 4-18ppm | ||
| Cyanuric Acid: | <30 | <30 |
| Must be less than 80 ppm | ||
| pH: | 7.4 | 7.6 |
| Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
||
| Total Alkalinity: | 70 | 60 |
| Calcium Hardness: | 170 | 170 |
| Name: | Outdoor Pool >= 1500 sq ft | Out. Wading Pool |
|---|---|---|
| Registration No: | SP57-015-100 | SP57-015-101 |
| Temperature (F): | 80.4 | 80.4 |
| Spa must not exceed 104° | ||
| Type of Disinfectant: | CO2 Cal Hypo | CO2 Cal Hypo |
| Disinfection make and model: | Pulsar Precision | Pulsar Precision |
| Drain Cover make and model: | Custom | Waterway |
| Drain Cover exp. date: | 05/04/2030 | 05/01/2030 |
| CPO: | Dana/Valerie | Dana/Valerie |
| CPO exp. date: | 11/30/2027 | 11/30/2027 |
| 1. Facility in compliance with smoking ban? | |
| ( If no, complete complaint form ) | |
Notes: Routine inspection.
Add monthly GFCI and emergency phone testing to operations log.
Recommend adding more 4x4 to the first aid kit, only one remaining.
Recommend replacing water slide rules sign that is fading.
Ensure custom VGB drain cover information is readily available.
Please email a letter of correction stating how the violations listed below have been and/or will be corrected to Todd.Jewell@linncountyiowa.gov within 30 days of this inspection.
| # | Section | Reference | Ref. Page | |
|---|---|---|---|---|
| 1) | Management/Personnel | Pool: | 15.4(6)f(6) | 24 |
| Spa: | 15:51(5)e(8) | 17 | ||
| Item: Monthly ground fault circuit interrupter (GFCI) testing shall be included in pool logs | ||||
| Comment: Perform monthly GFCI testing and document in your operations log. | ||||
| 2) | Management/Personnel | Pool: | 15.4(6)i | 25 |
| Spa: | 15.51(5)g | 18 | ||
| Item: A permanent manual of operation shall be kept in facility | ||||
| Comment: Please test emergency phone monthly and document in your operations log. | ||||
| 3) | Decks | Pool: | 15.4(4)k(1) | 21 |
| Spa: | 15.51(4)h(1) | 15 | ||
| Item: Pool and Spa decks shall be maintained slip-resistant, and free of litter, obstructions and tripping hazards. | ||||
| Comment: Please ensure lounge chairs are at least 4 feet away from the edge of the pool. | ||||
| Name | Date | ||
|---|---|---|---|
| Inspector: | Inspection: | ||
| Report Received By: | Received: | ||
| Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).