Swimming Pool / Spa Inspection Report Jones County Environmental Services 105 Broadway Place, Suite 11 Anamosa, IA 52205 Phone: (319) 462-4715 Fax: (319) 462-5302 E-mail: environmental@co.jones.ia.us |
Facility Name: Monticello Aquatic Center
Title: CPO Registration No: SP53-002-100 \ SP53-002-101 \ SP53-002-102 Type: Routine |
Name: | Out. Pool >= 1500 | Out. Wad > 500 | Out. Waterslide |
---|---|---|---|
Registration No: | SP53-002-100 | SP53-002-101 | SP53-002-102 |
Area (Sq. ft.): | 6000 | 900 | |
Volume (Gallons): | 40000 | ||
Filter Type: | Sand Zone 1 | Sand Zone 2 | |
Filter Rate: | |||
Turnover Rate: | |||
Chlorine (Free): | 2.4 | 4 | |
ORP: | 7.3/802/84 | 7.4/755/83 | |
Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
|||
Chlorine (Total): | 2.6 | 4.2 | |
Chlorine (Combined): | 0.2 | 0.2 | |
Bromine: | NA | NA | |
Pool: 2-18ppm Spa: 4-18ppm | |||
Cyanuric Acid: | <30 | <30 | |
Must be less than 80 ppm | |||
pH: | 7.4 | 7.2 | |
Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
|||
Total Alkalinity: | 40 | 40 | |
Calcium Hardness: | 520 | 500 |
Name: | Out. Pool >= 1500 | Out. Wad > 500 | Out. Waterslide |
---|---|---|---|
Registration No: | SP53-002-100 | SP53-002-101 | SP53-002-102 |
Temperature (F): | 84 | 83 | |
Spa must not exceed 104° | |||
Type of Disinfectant: | Cal Hypo Briquettes | Cal Hypo Briquettes | |
Disinfection make and model: | BECSYS5/Pulsar Precision | BECSYS5/Pulsar Precision | |
Drain Cover make and model: | Waterway | Waterway | |
Drain Cover exp. date: | ? | ? | |
CPO: | Jacob Oswald | Same | |
CPO exp. date: | 4/30/2027 | Same |
1. Facility in compliance with smoking ban? | |
( If no, complete complaint form ) |
Notes: Routine inspection.
Recommend replacing the seatbelt straps on the spine board to prevent burns in the event of an emergency.
Please ensure the EAP is easily accessible in case of emergency.
Please email a letter of correction stating how the violations listed below have been and/or will be corrected to Emily.Forde@linncountyiowa.gov within 30 days of this inspection.
# | Section | Reference | Ref. Page | |
---|---|---|---|---|
1) | Safety | Pool: | 15.4(4)h | 18 and 19 |
Item: All drains shall be VGB compliant and within their life expectancy date | ||||
Comment: Unable to locate at time of inspection. Expiration date from last inspection listed as 5/11/2024. | ||||
2) | Safety | Pool: | 15.4(4)d(5) | 16 |
Item: Each water slide shall have a minimum of two attendants, one stationed at the top of the slide and one at the bottom of the slide. | ||||
Comment: Please ensure there are guards at the top and bottom of the waterslide. If this is not possible, please close the slide. | ||||
3) | Showers/Toilets/Dressing Rooms | Pool: | 15.4(5)e | 23 |
Item: Soap shall be available at each lavatory and at each indoor shower fixture. | ||||
Comment: Please add soap to women's locker room shower. | ||||
Name | Date | ||
---|---|---|---|
Inspector: | Inspection: | ||
Report Received By: | Received: | ||
Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).