Swimming Pool / Spa
Inspection Report


Linn County Public Health
1020 - 6th Street SE
Cedar Rapids, IA 52401
Phone: (319) 892-6000 Fax: (319) 892-6099
E-mail: health@linncountyiowa.gov
  Facility Name: Midwest Athletic Club
Address: 4700 Tama Street SE Suite 100
Cedar Rapids, IA  52403
Person Contacted: Unknown
Title: N/A
Registration No: SP57-101-100 \ SP57-101-101
Type: Complaint

Water Quality Information
Name: Ind. Pool < 1500 Indoor Spa
Registration No: SP57-101-100 SP57-101-101
Area (Sq. ft.): 1498 80
Volume (Gallons): 50400 1328
Filter Type:
Filter Rate:
Turnover Rate:
Chlorine (Free): 4.8
ORP: 793
Pool: 1-8ppm, ORP 700-880 mV
If less than 0.6ppm or greater than 8.0ppm = closure
Spa: 2-8 ppm ORP 700-880 mV
If less than 1.0ppm or greater than 8.0ppm = closure
Chlorine (Total):
Chlorine (Combined):
Bromine:
Pool: 2-18ppm Spa: 4-18ppm
Cyanuric Acid:
Must be less than 80 ppm
pH: HIGH
Pool and Spa: 7.2ppm-7.8ppm
If less than 6.8 or greater than 8.2 = closure
Total Alkalinity:
Calcium Hardness:

 

Water Quality Information (continued)
Name: Ind. Pool < 1500 Indoor Spa
Registration No: SP57-101-100 SP57-101-101
Temperature (F): 101.8
Spa must not exceed 104°
Type of Disinfectant:
Disinfection make and model:
Drain Cover make and model:
Drain Cover exp. date:
CPO:
CPO exp. date:

Smoke Free Air Act
1. Facility in compliance with smoking ban?
( If no, complete complaint form )

Notes: Drop in inspection due to a complaint stating the spa was unclean.

pH tested high leading to closure of the spa at this time.

Spa will be closed until chemistry is back in safe ranges.

# Section Reference Ref. Page
1) Management/Personnel Pool: 15.4(2)e 8
Spa: 15.51(2)e 11 and 12
  Item: The disinfectant and pH in the pool water shall be manually tested and documented each day within one-half hour of the pool opening and at least one other time throughout the day. Chlorine shall be between 1.0 & 8.0 and pH shall be between 7.0 & 7.8. If either of these levels are out of range, the pool shall be closed.
  Comment: Ensure two manual tests per day. Please record ORP readings every 2 hours.
   
2) Water Quality Pool: 15.4(2)b 10
Spa: 15.51(2)b 10
  Item: The pH level of a spa / pool shall be 7.2 to 7.8
  Comment: PH tested higher than 8.0ppm.
   
  Name   Date
Inspector: Inspection:
     
Report Received By: Received:
Reviewed By: Reviewed:

These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).