Swimming Pool / Spa Inspection Report Linn County Public Health 1020 - 6th Street SE Cedar Rapids, IA 52401 Phone: (319) 892-6000 Fax: (319) 892-6099 E-mail: health@linncountyiowa.gov |
Facility Name: Cedar Rapids Residence Inn
Title: CPO Registration No: SP57-072-100 \ SP57-072-101 Type: Routine |
Name: | Indoor Pool < 1500 sq ft | Indoor Spa |
---|---|---|
Registration No: | SP57-072-100 | SP57-072-101 |
Area (Sq. ft.): | 490 | 54 |
Volume (Gallons): | 12795 | 1100 |
Filter Type: | Sand | Sand |
Filter Rate: | ||
Turnover Rate: | ||
Chlorine (Free): | 2.0 | 8.0 |
ORP: | 701 / 7.42 | 724 / 7.30 |
Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
||
Chlorine (Total): | 2.6 | 8.2 |
Chlorine (Combined): | 0.6 | 0.2 |
Bromine: | NA | NA |
Pool: 2-18ppm Spa: 4-18ppm | ||
Cyanuric Acid: | NA | NA |
Must be less than 80 ppm | ||
pH: | 7.0 | 7.6 |
Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
||
Total Alkalinity: | 40 | 70 |
Calcium Hardness: | 300 | 260 |
Name: | Indoor Pool < 1500 sq ft | Indoor Spa |
---|---|---|
Registration No: | SP57-072-100 | SP57-072-101 |
Temperature (F): | 82.9 | 102.7 |
Spa must not exceed 104° | ||
Type of Disinfectant: | Chlorine Puck | Chlorine Puck |
Disinfection make and model: | EcoLab N0290 | EcoLab N-290 |
Drain Cover make and model: | Aquastar | Hayward |
Drain Cover exp. date: | 1/13/2027 | 1/13/2029 |
CPO: | Angee Booth | Same |
CPO exp. date: |
1. Facility in compliance with smoking ban? | |
( If no, complete complaint form ) |
Notes: :
Routine inspection today.
Please email a letter of correction stating how the violations listed below have been and/or will be corrected to diane.midcalf@linncountyiowa.gov within 30 days of this inspection.
Also note that the probes are not reading the water accurately and either need cleaned or replaced. Please call Ecolab for service asap.
And be sure to document GFCI testing/cleaning/backwashing/draining/adding chemicals to pool on logs.
# | Section | Reference | Ref. Page | |
---|---|---|---|---|
1) | Filtration/Recirculation | Pool: | 15.4(1)b(4) | 8 |
Spa: | 15.51(1)e | 9 | ||
Item: Skimmer shall have an easily removable basket/screen upstream from any valve and have a Self-adjusting weir in place | ||||
Comment: Replace missing weir | ||||
2) | Water Quality | Pool: | 15.4(1)a | 8 |
Spa: | 15.51(1)a | 8 | ||
Item: A pool / spa filtration system shall be in working order and provide water clarity up to code standards, without leakage. | ||||
Comment: Spa area has a leak that needs addressed. | ||||
3) | Safety | Pool: | 15.4(4)a(5) | 14 |
Spa: | 15.51(4)a(5) | 13 | ||
Item: A chemical hazard warning sign shall be placed at the entrance of a room where chemicals are used or stored or where bulk containers are located. | ||||
Comment: Add one to filter room door | ||||
4) | Safety | Pool: | 15.4(4)m(2) | 17 |
Item: Fully submerged lighting in a pool or spa shall be in working order. | ||||
Comment: Have Bob replace bulb in pool | ||||
Name | Date | ||
---|---|---|---|
Inspector: | Inspection: | ||
Report Received By: | Received: | ||
Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).