Swimming Pool / Spa Inspection Report Linn County Public Health 1020 - 6th Street SE Cedar Rapids, IA 52401 Phone: (319) 892-6000 Fax: (319) 892-6099 E-mail: health@linncountyiowa.gov |
Facility Name: Keystone Place
Title: CPO Registration No: SP57-104-100 \ SP57-104-101 Type: Routine |
Name: | Indoor Pool < 1500 sq ft | Indoor Spa |
---|---|---|
Registration No: | SP57-104-100 | SP57-104-101 |
Area (Sq. ft.): | 450 | 48 |
Volume (Gallons): | 12350 | 900 |
Filter Type: | Sand | Sand |
Filter Rate: | XX | XX |
Turnover Rate: | XX | XX |
Chlorine (Free): | 1.0 | 3.6 |
ORP: | 753 / 7.5 | 797 / 7.6 |
Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
||
Chlorine (Total): | 1.2 | 3.8 |
Chlorine (Combined): | 0.2 | 0.2 |
Bromine: | NA | NA |
Pool: 2-18ppm Spa: 4-18ppm | ||
Cyanuric Acid: | NA | NA |
Must be less than 80 ppm | ||
pH: | 7.6 | 7.4 |
Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
||
Total Alkalinity: | 40 | 40 |
Calcium Hardness: | 1370 | > 1400 |
Name: | Indoor Pool < 1500 sq ft | Indoor Spa |
---|---|---|
Registration No: | SP57-104-100 | SP57-104-101 |
Temperature (F): | 86 | 99.7 |
Spa must not exceed 104° | ||
Type of Disinfectant: | CHLORINE | CHLORINE |
Disinfection make and model: | PULSAR PRECISION 30 | PULSAR PRECISION 30 |
Drain Cover make and model: | HAYWARD | HAYWARD |
Drain Cover exp. date: | 9/14/2024 | 9/14/2024 |
CPO: | RICK PALVIS | LISA TRUNNELL |
CPO exp. date: | 11/18/2025 | 11/18/2025 |
1. Facility in compliance with smoking ban? | |
( If no, complete complaint form ) |
Notes: :
Routine inspection today
Please email a letter of correction stating how the violations listed below have been and/or will be corrected to diane.midcalf@linncountyiowa.gov within 30 days of this inspection.
Also, please address the spaces where there is an abundance of corrosion. This is indicative of leaks. Fix the leaks and clean off the corrosion.
# | Section | Reference | Ref. Page | |
---|---|---|---|---|
1) | Filtration/Recirculation | Pool: | 15.4(1)b(2) | 8 |
Spa: | 15.51(1)a(4) | 8 | ||
Item: Recirculation system shall have an operating gauge installed in the proper location near filter | ||||
Comment: Replace all pressure gauges that are blackened and not legible. I believe there are 5 of thwem. | ||||
2) | Safety | Spa: | 15.51(4)l | 16 |
Item: The agitation system control (timer) shall be installed out of the reach of persons in the spa. The "on" cycle for the agitation system shall be no more than ten minutes | ||||
Comment: Timer runs for > 10 minutes, replace | ||||
Name | Date | ||
---|---|---|---|
Inspector: | Inspection: | ||
Report Received By: | Received: | ||
Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).