Swimming Pool / Spa Inspection Report Linn County Public Health 1020 - 6th Street SE Cedar Rapids, IA 52401 Phone: (319) 892-6000 Fax: (319) 892-6099 E-mail: health@linncountyiowa.gov |
Facility Name: Cedar Rapids Marriott
Title: Supervising Engineer - CPO Registration No: SP57-067-100 \ SP57-067-101 Type: Routine |
Name: | Indoor Pool < 1500 sq ft | Indoor Spa2 |
---|---|---|
Registration No: | SP57-067-100 | SP57-067-101 |
Area (Sq. ft.): | 800 | 19 |
Volume (Gallons): | 24000 | 56 |
Filter Type: | Sand | Sand |
Filter Rate: | ||
Turnover Rate: | ||
Chlorine (Free): | 2.0 | 2.8 |
ORP: | 723 | 721 |
Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
||
Chlorine (Total): | 2.2 | 4.2 |
Chlorine (Combined): | 0.2 | 1.4 |
Bromine: | NA | NA |
Pool: 2-18ppm Spa: 4-18ppm | ||
Cyanuric Acid: | NA | NA |
Must be less than 80 ppm | ||
pH: | 7.4 | 7.4 |
Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
||
Total Alkalinity: | 90 | 40 |
Calcium Hardness: | 640 | 200 |
Name: | Indoor Pool < 1500 sq ft | Indoor Spa2 |
---|---|---|
Registration No: | SP57-067-100 | SP57-067-101 |
Temperature (F): | 85.9 | 103.8 |
Spa must not exceed 104° | ||
Type of Disinfectant: | Chlorine Pucks | Liquid Chlorine |
Disinfection make and model: | EcoLab N290 | Liquid Aqua Balance |
Drain Cover make and model: | Hayward | Hayward |
Drain Cover exp. date: | 9/9/2029 | 9.9.2029 |
CPO: | ||
CPO exp. date: |
1. Facility in compliance with smoking ban? | |
( If no, complete complaint form ) |
Notes: :
Please email a letter of correction stating how the violations listed below have been and/or will be corrected to diane.midcalf@linncountyiowa.gov within 30 days of this inspection.
Also, please make sure all gauges are in working order, and that the water flow direction is indicated on pipes in pump room, along with documenting when the spa is drained and GFCI outlets are tested.
# | Section | Reference | Ref. Page | |
---|---|---|---|---|
1) | Safety | Pool: | 15.4(4)b(2) | 13 |
Item: Pool ladders, ramps, handrails, and grab rails shall be securely anchored. | ||||
Comment: Ladder needs tightened | ||||
2) | Safety | Pool: | 15.4(6)k | 25 |
Spa: | 15.51(5)i | 18 | ||
Item: Each member of staff shall sign off that they have reviewed SDS sheets along with the Emergency Action Plan annually. | ||||
3) | Safety | Pool: | 15.4(4)m(2) | 17 |
Item: Fully submerged lighting in a pool or spa shall be in working order. | ||||
Name | Date | ||
---|---|---|---|
Inspector: | Inspection: | ||
Report Received By: | Received: | ||
Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).