Swimming Pool / Spa
Inspection Report


Linn County Public Health
1020 - 6th Street SE
Cedar Rapids, IA 52401
Phone: (319) 892-6000 Fax: (319) 892-6099
E-mail: health@linncountyiowa.gov
  Facility Name: Wheatland Club Apts
Address: 5617 Muirfield Dr SW
Cedar Rapids, IA  52404
Person Contacted: Antrell Williams
Title: Facilities Manager
Registration No: SP57-107-100
Type: Routine

Water Quality Information
Name: Outdoor Pool < 1500 sq ft
Registration No: SP57-107-100
Area (Sq. ft.): 800
Volume (Gallons): 25600
Filter Type: Sand
Filter Rate:
Turnover Rate:
Chlorine (Free): 0.6
ORP: 571 / 7.9
Pool: 1-8ppm, ORP 700-880 mV
If less than 0.6ppm or greater than 8.0ppm = closure
Spa: 2-8 ppm ORP 700-880 mV
If less than 1.0ppm or greater than 8.0ppm = closure
Chlorine (Total): 0.6
Chlorine (Combined): 0
Bromine: NA
Pool: 2-18ppm Spa: 4-18ppm
Water Quality Information (continued)
Cyanuric Acid: 40
Must be less than 80 ppm
pH: 7.6
Pool and Spa: 7.2ppm-7.8ppm
If less than 6.8 or greater than 8.2 = closure
Total Alkalinity: 40
Calcium Hardness: 230
Temperature (F): 84.1
Spa must not exceed 104°
Type of Disinfectant: Chlorine
Disinfection make and model: Accu-TAB
Drain Cover make and model: Unknown
Drain Cover exp. date: Unknown
CPO:
CPO exp. date:

Smoke Free Air Act
1. Facility in compliance with smoking ban?
( If no, complete complaint form )

Notes: :
Pool closed by inspector at routine inspection due to low chlorine and ORP. Once the chlorine is between 1.0 and 7.8 and the ORP is between 660 and 880, text me a picture of the controller and you may reopen. Be sure that the levels are between these parameters at all times the pool is open.

Please email a letter of correction stating how the other violations listed below have been and/or will be corrected to diane.midcalf@linncountyiowa.gov within 30 days of this inspection. Thank you.

# Section Reference Ref. Page
1) Filtration/Recirculation Pool: 15.4(1)b(2) 8
Spa: 15.51(1)a(4) 8
  Item: Recirculation system shall have an operating gauge installed in the proper location near filter
  Comment: This is installed, but on the high end today. It looks like you are only backwashing once per week. I would recommend increasing that to twice per week to keep that number below 20.
   
2) Safety Pool: 15.4(4)h 18 and 19
  Item: All drains shall be VGB compliant and within their life expectancy date
  Comment: Please provide the VGB installation date, expiration date and make/model.
   
3) Safety Pool: 15.4(6)k 25
Spa: 15.51(5)i 18
  Item: Each member of staff shall sign off that they have reviewed SDS sheets along with the Emergency Action Plan annually.
   
  Name   Date
Inspector: Inspection:
     
Report Received By: Received:
Reviewed By: Reviewed:

These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).