Swimming Pool / Spa Inspection Report Linn County Public Health 1020 - 6th Street SE Cedar Rapids, IA 52401 Phone: (319) 892-6000 Fax: (319) 892-6099 E-mail: health@linncountyiowa.gov |
Facility Name: Elmcrest Country Club
Title: CPO Registration No: SP57-015-100 \ SP57-015-101 Type: Routine |
Name: | Outdoor Pool >= 1500 sq ft | Out. Wading Pool |
---|---|---|
Registration No: | SP57-015-100 | SP57-015-101 |
Area (Sq. ft.): | > 1500 | > 1500 |
Volume (Gallons): | 154000 | 2500 |
Filter Type: | Sand | Sand |
Filter Rate: | ||
Turnover Rate: | ||
Chlorine (Free): | 0.6 | 0.6 |
ORP: | 747 / 7.6 | 703 / 7.6 |
Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
||
Chlorine (Total): | 0.6 | 0.8 |
Chlorine (Combined): | 0.2 | 0 |
Bromine: | NA | NA |
Pool: 2-18ppm Spa: 4-18ppm | ||
Cyanuric Acid: | <30 | <30 |
Must be less than 80 ppm | ||
pH: | 7.4 | 7.6 |
Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
||
Total Alkalinity: | 80 | 70 |
Calcium Hardness: | 300 | 330 |
Name: | Outdoor Pool >= 1500 sq ft | Out. Wading Pool |
---|---|---|
Registration No: | SP57-015-100 | SP57-015-101 |
Temperature (F): | 86.3 | 85 |
Spa must not exceed 104° | ||
Type of Disinfectant: | Chlorine | Chlorine |
Disinfection make and model: | Accutab | Accutab |
Drain Cover make and model: | Custom, installed 05/09 | Unknown |
Drain Cover exp. date: | 05/29 Hardware and Cover | Unknown |
CPO: | ||
CPO exp. date: |
1. Facility in compliance with smoking ban? | |
( If no, complete complaint form ) |
Notes: :
Chlorine is extremely low today. Please address asap.
Please see lifeguard note below and work on some sort of set expectations in regards to a rotation of guards, zones, and making sure the entire pool can be seen by a guard at all times of operation.
Please email a letter of correction stating how the violations listed below have been and/or will be corrected to diane.midcalf@linncountyiowa.gov within 30 days of this inspection.
# | Section | Reference | Ref. Page | |
---|---|---|---|---|
1) | Management/Personnel | Pool: | 15.4(6)m | 25 |
Item: A lifeguard staffing plan shall be available | ||||
Comment: For the size of the pool I recommend that there is a lifeguard in each chair and one in the zero depth area at all times there are individuals in those areas. But, because this is a country club, it is exempt of the rule that lifeguards are required. If you ever decide to not staff the pool with lifeguards (not recommended), be sure to post signs at the gate and throughout the facility stating 'NO LIFEGUARD ON DUTY'. Without these signs posted, it is presumed you have lifeguards. | ||||
2) | Water Quality | Pool: | 15.4(2)a(1) | 9 |
Item: Pool water shall have a free chlorine residual of at least 1.0 ppm and no greater than 8.0 ppm, or a total bromine residual of at least 2.0 ppm and no greater than 18.0 ppm when pool is in use | ||||
Comment: Chlorine is extremely low today. Poollog shows many incidents that the chlorine level was too low to be open, but pool was not closed. Staff needs retrained as to what the appropriate chemical levels are and to call the CPO when they are out of range and close the pool. | ||||
3) | Decks | Pool: | 15.5(4)a | 29 |
Item: A swimming pool shall be surrounded by a deck. The deck shall be at least 6 ft. wide for a Class A swimming pool, and 4 ft. wide for a Class B swimming pool, and shall extend at least 4 ft. beyond the diving stands, lifeguard chairs, swimming pool slides, or any other deck equipment. | ||||
Comment: Please make sure that there is a clear, walkable path on the outside of the entire pool area. Chairs should be pushed back to ensure a safe walkway. | ||||
4) | Safety | Pool: | 15.4(4)h | 18 and 19 |
Item: All drains shall be VGB compliant and within their life expectancy date | ||||
Comment: VGB in shallow water is in good repair, removed every winter and reinstalled each spring, but expired 5/2022. Facility will order a new one and replace by spring 2023. | ||||
5) | Structure/Diving | Pool: | 15.4(4)c(10) | 14 |
Item: Supports, platforms, and steps for diving boards shall be of substantial construction and of sufficient structural strength to safely carry the maximum anticipated load. | ||||
Comment: Diving board is not secure, please fix. | ||||
Name | Date | ||
---|---|---|---|
Inspector: | Inspection: | ||
Report Received By: | Received: | ||
Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).