Swimming Pool / Spa Inspection Report Jones County Environmental Services 105 Broadway Place, Suite 11 Anamosa, IA 52205 Phone: (319) 462-4715 Fax: (319) 462-5302 E-mail: environmental@co.jones.ia.us |
Facility Name: Anamosa Aqua Court
Title: N/A Registration No: SP53-007-100 \ SP53-007-102 \ SP53-007-101 Type: Routine |
Name: | Out. Pool >= 1500 | Out. Wading | Out. Waterslide |
---|---|---|---|
Registration No: | SP53-007-100 | SP53-007-102 | SP53-007-101 |
Area (Sq. ft.): | |||
Volume (Gallons): | 200000 | 3675 | |
Filter Type: | Sand | Sand | |
Filter Rate: | |||
Turnover Rate: | |||
Chlorine (Free): | 2.68 | 2.68 | |
ORP: | |||
Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
|||
Chlorine (Total): | 2.78 | 2.78 | |
Chlorine (Combined): | .1 | .1 | |
Bromine: | |||
Pool: 2-18ppm Spa: 4-18ppm | |||
Cyanuric Acid: | 5 | 5 | |
Must be less than 80 ppm | |||
pH: | 6.9 | 6.9 | |
Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
|||
Total Alkalinity: | 69 | 69 | |
Calcium Hardness: | 122 | 122 |
Name: | Out. Pool >= 1500 | Out. Wading | Out. Waterslide |
---|---|---|---|
Registration No: | SP53-007-100 | SP53-007-102 | SP53-007-101 |
Temperature (F): | |||
Spa must not exceed 104° | |||
Type of Disinfectant: | Chlorine | Chlorine | |
Disinfection make and model: | |||
Drain Cover make and model: | |||
Drain Cover exp. date: | |||
CPO: | |||
CPO exp. date: |
1. Facility in compliance with smoking ban? | |
( If no, complete complaint form ) |
Notes: Baby pool was closed at time of inspection due to bad water quality.
# | Section | Reference | Ref. Page | |
---|---|---|---|---|
1) | Management/Personnel | Pool: | 15.4(6)f(6) | 24 |
Spa: | 15:51(5)e(8) | 17 | ||
Item: Monthly ground fault circuit interrupter (GFCI) shall be included in Operational Records | ||||
Comment: GFCI testing was not being recorded in log book. | ||||
2) | Management/Personnel | Pool: | 15.4(6)i | 25 |
Spa: | 15.51(5)g | 18 | ||
Item: A permanent manual of operation shall be kept in facility | ||||
Comment: Procedures for superchlorination, backwashing, and vacuuming the pool are not written. | ||||
3) | Decks | Pool: | 15.4(4)k(1) | 21 |
Spa: | 15.51(4)h(1) | 15 | ||
Item: Pool and Spa decks shall be maintained slip-resistant, and free of litter, obstructions and tripping hazards. | ||||
Comment: Deck is heaving and settling by the slide and diving boards. | ||||
4) | Safety | Pool: | 15.4(4)f(4) | 17 |
Item: A first-aid kit shall be equipped with: band-aids, sterile 4x4 bandage compress, self-adhering gauze bandage, disposable gloves, and a chemical cold press. | ||||
Comment: First aid kit is missing cold packs. | ||||
5) | Safety | Pool: | 15.4(4)l(2) | 21 |
Spa: | 15.51(4)k(2) | 16 | ||
Item: A fence, wall, or other means of enclosure shall have no openings that would allow the passage of a 4-inch sphere, and shall not be easily climbable by toddlers. | ||||
Comment: Fence on the west side (gate opening) has a gap larger than 4 inches. | ||||
Name | Date | ||
---|---|---|---|
Inspector: | Inspection: | ||
Report Received By: | Received: | ||
Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).