Swimming Pool / Spa Inspection Report Jones County Environmental Services 105 Broadway Place, Suite 11 Anamosa, IA 52205 Phone: (319) 462-4715 Fax: (319) 462-5302 E-mail: environmental@co.jones.ia.us |
Facility Name: Anamosa Aqua Court
Title: CPO & Manager Registration No: SP53-007-100 \ SP53-007-102 \ SP53-007-101 Type: Routine |
Name: | Out. Pool >= 1500 | Out. Wading | Out. Waterslide |
---|---|---|---|
Registration No: | SP53-007-100 | SP53-007-102 | SP53-007-101 |
Area (Sq. ft.): | |||
Volume (Gallons): | 200000 | 3675 | |
Filter Type: | Sand | ||
Filter Rate: | |||
Turnover Rate: | |||
Chlorine (Free): | 5.32 | 6.08 | 5.93 |
ORP: | 703 | ||
Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
|||
Chlorine (Total): | 5.51 | 6.27 | 5.93 |
Chlorine (Combined): | 0.19 | 0.19 | 0 |
Bromine: | |||
Pool: 2-18ppm Spa: 4-18ppm | |||
Cyanuric Acid: | 27 | 26 | 22 |
Must be less than 80 ppm | |||
pH: | 7.3 | 7.2 | 8.0 |
Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
|||
Total Alkalinity: | 58 | 56 | 116 |
Calcium Hardness: | 452 | 478 | 613 |
Name: | Out. Pool >= 1500 | Out. Wading | Out. Waterslide |
---|---|---|---|
Registration No: | SP53-007-100 | SP53-007-102 | SP53-007-101 |
Temperature (F): | |||
Spa must not exceed 104° | |||
Type of Disinfectant: | Chlorine | ||
Disinfection make and model: | |||
Drain Cover make and model: | |||
Drain Cover exp. date: | |||
CPO: | |||
CPO exp. date: |
1. Facility in compliance with smoking ban? | |
( If no, complete complaint form ) |
Notes: Scott said the backwash drain line was repaired ~2 years ago to connect waste water to City Sewer with a bigger drain line allowing water to adequately drain. There is a connection to drain backwash into near by creek, but facility does not drain into creek often and if does, they ensure all chlorine is out of water supply before.
If continue to drain backwash into creek, MUST OBTAIN A PERMIT "Storm Water Discharge" FROM DNR.
Closing wading pool after this year (ADA Requirements not meet).
# | Section | Reference | Ref. Page | |
---|---|---|---|---|
1) | Management/Personnel | Pool: | 15.4(6)f | 24 |
Spa: | 15.51(5)e | 17 | ||
Item: Records shall include results of chemical tests, results of microbial analyses, reports of complaints/injuries/illnesses, daily water temp. (spa), dates of draining/cleaning, and dates of review of MSDS | ||||
Comment: Must supply a microbial water sample for month of May even if open for only 2 days. | ||||
2) | Management/Personnel | Pool: | 15.4(2)e | 10 and 11 |
Spa: | 15.51(2)e | 11 and 12 | ||
Item: Not tested/recorded as often as necessary in Operation Records | ||||
Comment: Must record weekly testing of combined chlorine total Alkalinity, Cyanuric Acid and monthly test of Calcium Hardness for baby pool (wading). | ||||
3) | Decks | Pool: | 15.4(1)d(2) | 29 |
Spa: | 15.51(4)h(3) | 15 | ||
Item: A hose bib shall be provided for flushing or cleaning of the deck. Each hose bib at a Facility shall be equipped with an atmospheric vacuum breaker or a hose connection backflow preventer. | ||||
Comment: Hose bib connection near filter room needs an atmospheric vacuum breaker. | ||||
4) | Safety | Pool: | 15.4(4)f(4) | 17 |
Item: A first-aid kit shall be equipped with: band-aids, sterile 4x4 bandage compress, self-adhering gauze bandage, disposable gloves, and a chemical cold press. | ||||
Comment: First aid kit missing chemical cold press. | ||||
5) | Safety | Pool: | 15.4(4)b(2) | 13 |
Item: Pool ladders, ramps, handrails, and grab rails shall be securely anchored. | ||||
Comment: Secure ladder by 3 foot 10 inch marker and 5 foot marker. | ||||
6) | Safety | Pool: | 15.4(4)m(1) | 22 |
Spa: | 15.51(4)j(1) | 15 | ||
Item: Each electrical outlet in the deck, shower room, and pool water treatment equipment areas of a swimming pool or spa shall be equipped with a properly installed ground fault circuit interrupter (GFCI) at the outlet or at the breaker serving the outlet, and shall be tested at least once a month. Testing dates and results shall be recorded in the pool records. | ||||
Comment: GFCI outlet by lockers is taped shut. Continues to not work properly. Repair. | ||||
Name | Date | ||
---|---|---|---|
Inspector: | Inspection: | ||
Report Received By: | Received: | ||
Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).