Swimming Pool / Spa Inspection Report Jones County Environmental Services 105 Broadway Place, Suite 11 Anamosa, IA 52205 Phone: (319) 462-4715 Fax: (319) 462-5302 E-mail: environmental@co.jones.ia.us |
Facility Name: Anamosa Aqua Court
Title: Manager Registration No: SP53-007-100 \ SP53-007-102 \ SP53-007-101 Type: Routine |
Name: | Out. Pool >= 1500 | Out. Wading | Out. Waterslide |
---|---|---|---|
Registration No: | SP53-007-100 | SP53-007-102 | SP53-007-101 |
Area (Sq. ft.): | |||
Volume (Gallons): | 200000 | 3675 | |
Filter Type: | Sand | ||
Filter Rate: | |||
Turnover Rate: | |||
Chlorine (Free): | 1.66 | 3.36 | |
ORP: | 770 | ||
Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
|||
Chlorine (Total): | 2.11 | 4.11 | |
Chlorine (Combined): | 0.45 | 0.75 | |
Bromine: | N/A | ||
Pool: 2-18ppm Spa: 4-18ppm | |||
Cyanuric Acid: | 14 | 8 | |
Must be less than 80 ppm | |||
pH: | 7.3 | 7.4 | |
Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
|||
Total Alkalinity: | 54 | 35 | |
Calcium Hardness: | 222 | 306 |
Name: | Out. Pool >= 1500 | Out. Wading | Out. Waterslide |
---|---|---|---|
Registration No: | SP53-007-100 | SP53-007-102 | SP53-007-101 |
Temperature (F): | |||
Spa must not exceed 104° | |||
Type of Disinfectant: | chlorine | chlorine | |
Disinfection make and model: | |||
Drain Cover make and model: | |||
Drain Cover exp. date: | |||
CPO: | |||
CPO exp. date: |
1. Facility in compliance with smoking ban? | |
( If no, complete complaint form ) |
Notes: * Low alkalinity -> may lead to pH variability and corrosion.
# | Section | Reference | Ref. Page | |
---|---|---|---|---|
1) | Management/Personnel | Pool: | 15.4(2)e | 10 and 11 |
Spa: | 15.51(2)e | 11 and 12 | ||
Item: Manual tests are not being conducted as often as necessary | ||||
Comment: Must test Alkalinity and Combined Chlorine weekly for main pool. Also Cyanuric Acid monthly. REPEAT VIOLATION. Correct immediately. | ||||
2) | Safety | Pool: | 15.4(4)b(2) | 13 |
Item: Pool ladders, ramps, handrails, and grab rails shall be securely anchored. | ||||
Comment: Secure ladder at 5 foot mark and replace missing white end cap. REPEAT VIOLATION. | ||||
3) | Showers/Toilets/Dressing Rooms | Pool: | 15.4(5)e | 23 |
Item: Soap shall be available at each lavatory and at each indoor shower fixture. | ||||
Comment: Provide soap for all showers in locker rooms. | ||||
Name | Date | ||
---|---|---|---|
Inspector: | Inspection: | ||
Report Received By: | Received: | ||
Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).