Swimming Pool / Spa Inspection Report Linn County Public Health 1020 - 6th Street SE Cedar Rapids, IA 52401 Phone: (319) 892-6000 Fax: (319) 892-6099 E-mail: health@linncountyiowa.gov |
Facility Name: Aspen Athletic Club
Title: CPO Registration No: SP57-012-100 \ SP57-012-101 Type: Routine |
Name: | Indoor Pool >= 1500 sq ft | Indoor Spa |
---|---|---|
Registration No: | SP57-012-100 | SP57-012-101 |
Area (Sq. ft.): | 1800 | 0 |
Volume (Gallons): | 53640 | 0 |
Filter Type: | ||
Filter Rate: | ||
Turnover Rate: | ||
Chlorine (Free): | 3.6 | 6.0 |
ORP: | 744 | 750 |
Pool: 1-8ppm, ORP 700-880 mV If less than 0.6ppm or greater than 8.0ppm = closure Spa: 2-8 ppm ORP 700-880 mV If less than 1.0ppm or greater than 8.0ppm = closure |
||
Chlorine (Total): | 4.0 | 6.8 |
Chlorine (Combined): | 0.4 | 0.8 |
Bromine: | ||
Pool: 2-18ppm Spa: 4-18ppm | ||
Cyanuric Acid: | ||
Must be less than 80 ppm | ||
pH: | 7.6 | 7.8 |
Pool and Spa: 7.2ppm-7.8ppm If less than 6.8 or greater than 8.2 = closure |
||
Total Alkalinity: | 80 | 90 |
Calcium Hardness: |
Name: | Indoor Pool >= 1500 sq ft | Indoor Spa |
---|---|---|
Registration No: | SP57-012-100 | SP57-012-101 |
Temperature (F): | 101.4 | |
Spa must not exceed 104° | ||
Type of Disinfectant: | ||
Disinfection make and model: | ||
Drain Cover make and model: | ||
Drain Cover exp. date: | ||
CPO: | ||
CPO exp. date: |
1. Facility in compliance with smoking ban? | |
( If no, complete complaint form ) |
Notes: Facilities manager Justin stated that he would email copies of CPO certificate and main drain cover documentation once items are located.
# | Section | Reference | Ref. Page | |
---|---|---|---|---|
1) | Management/Personnel | Pool: | 15.4(6)a | 23 |
Spa: | 15.51(5)a | 16 | ||
Item: Certified Operator required | ||||
Comment: Was not able to verify certified pool operator certificate. Manager stated he was certified and would scan in and email copy of certificate to inspector. | ||||
2) | Management/Personnel | Pool: | 15.4(4)h(1) | 18 |
Spa: | 15.51(4)f | 14 | ||
Item: Main drain and Safety Vacuum Release System documentation (VGB) with dates of installation must be kept in facility. Each SVRS shall be tested monthly and the test dates recorded | ||||
Comment: Unable to find documentation for main drain covers in spa and pool that state dates of installation and VGB compliance. Must provide documentation. | ||||
Name | Date | ||
---|---|---|---|
Inspector: | Inspection: | ||
Report Received By: | Received: | ||
Reviewed By: | Reviewed: |
These items must be corrected as soon as possible in order to comply with the Iowa Department of Public Health Swimming Pool and Spa Rules. A letter regarding the actions which will be taken in order to correct all deficiencies must be submitted within 30 days to this office. If for any reason you take issue with any of the items cited regarding swimming pool rules, a variance can be requested by following the instructions in the Iowa Department of Public Health Swimming Pools manual, amended July 8th, 2009, page 57, section 641-15.7 (135I). Variance requests regarding spa rules must be made in compliance with the instructions in the Iowa Department of Public Health Spa manual, revised July 8th, 2009, page 32, section 641-15.7 (135I).